- Issue
- Journal of Siberian Federal University. Engineering & Technologies. 2016 9 (2)
- Authors
- Sizganova, Evgenia U.; Petukhov, Roman A.; Sizganov, Nikita V.; Nikotina, Daria U.
- Contact information
- Sizganova, Evgenia U.:Siberian Federal University 79 Svobodny, Krasnoyarsk, 660041, Russia; E-mail: ; Petukhov, Roman A.:Siberian Federal University 79 Svobodny, Krasnoyarsk, 660041, Russia; Sizganov, Nikita V.:Siberian Federal University 79 Svobodny, Krasnoyarsk, 660041, Russia; Nikotina, Daria U.:Siberian Federal University 79 Svobodny, Krasnoyarsk, 660041, Russia
- Keywords
- substation; shunt reactors; switching surges; auxiliary transformers; surge arresters; autotransformers; the current cutoff; replicate samples
- Abstract
The article considers the modeling and analysis of transient processes in a system of substation Zarya500 kV with different external conditions during commutation shunt reactor ROMBS-60000/500. Revealed that the high-frequency overvoltageduring switching shunt reactor of 500 kV, can be dangerous for air insulation transformers TSZ-630/15
- Pages
- 225-236
- Paper at repository of SibFU
- https://elib.sfu-kras.ru/handle/2311/20227
This work is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License (CC BY-NC 4.0).